@emilioheredia-source , this looks very interesting. Would you mind testing a case where a large number (>10) of non-trivial displays are open, maybe across multiple windows? The test should just shut down Phoebus and restart to recreate the displays as they were when shutting down (default Phoebus behavior). Reason I ask is to figure out how user experience would be affected, e.g. seemingly longer time to restore the view when launching Phoebus. |
|
Thanks, that was a good question. The test found a real slowdown, which is fixed now. Setup: 15 displays from the examples folder (10_scripts, 01_main, 11_datasources, 12_formulas, plots_xy, plots_image, structure_tabs, monitors_table, monitors_symbols, ...), 5 tabs in each of 3 windows, saved as the memento. Phoebus is started and restores them. I measured the time from launching Phoebus until the last display logged "Done with representing model", alternating master and the PR, on Xvfb with software rendering.
The first version was about 0.4 s slower. Each load went to the UI thread twice: once to dispose the shown display before loading, then again to represent the new one. At startup, the first layout pass of the restored windows ran in between, so every display waited for it. The new commit disposes the shown display and represents the new one in a single UI step, after the new display has been loaded, as master does for the representation. With that, restoring takes the same time as on master. One visible difference when navigating: the shown display now remains until the new one is ready, instead of being replaced by a "Loading ..." message right away. The first display of a tab still shows the message. In case it helps to judge the impact: we came across the leak while adding the mouse back/forward buttons for our operators, who navigate regularly with Back and Forward in EDM-style windows. A double click on the toolbar's Back button is enough to leave the skipped display's PVs connected until Phoebus exits. |
|
Thanks @emilioheredia-source I believe we have moved the file loading off the UI thread due to various performance issues discovered in BOY. This is particularly true if you have a bad script... That having being said the resource leak you point out is a serious bug.
Based on your finding the key issue here is that the job is not tracked properly. Instead of getting rid of the background loading could be make it into a proper cancellable job ( using I remember with BOY when the existing screen stayed visisble... instead of waiting users were inclined to keep pressing the button more and more - out of frustration - making matters worse. Again, we are quite glad you have discovered this |
caef31a to
e49520c
Compare
|
Thanks @shroffk, and sorry. You're right, and I should have asked before changing this. Reading the file did stay in the background job, but I changed when the old display goes away: it stayed on screen, still running, until the new one was ready, and loads in the same tab waited for each other. That throws away exactly the immediate feedback you describe from BOY. I made that change to win back the startup time Georg asked about, instead of stepping back to a smaller fix. The new version keeps the original flow as it was: the old display is removed and "Loading" is shown on the click, and the file is read in a background job, without loads waiting for each other and without the UI thread waiting for a load. The addition is what you suggested: the tab keeps track of its current load job (a Phoebus Restoring 15 displays in 3 windows takes the same time as on master. With history A, B, C and a double click on "back", master left B's runtime running or showed B; with this version A is shown and every runtime that started was stopped. One part needed a decision, and I'd like your opinion on it: a display runtime that is still starting can't be stopped ( |
…ckly loadDisplayFile() disposes the shown display, shows "Loading ...", and loads the new display in a background job, but nothing kept track of that job. When a second load started before the first one was done, for example on a double click on "back", both jobs represented their display and started its runtime: one runtime kept running with its PVs until exit, or the wrong display was shown. Closing the display while it loaded gave a "Cannot load model" error. Keep the load sequence as it is and track the load job: a new load or closing the display cancels it. A cancelled job doesn't represent its display or start its runtime, and its errors are only logged. The check before representing runs on the UI thread, where the cancellation happens. A display runtime that is starting can't be stopped. When the display is disposed during that start, the UI thread only disposes the representation, and the load job stops the runtime and disposes the model once the start is done. The UI thread never waits for it.
e49520c to
93dee88
Compare
|



Summary
DisplayRuntimeInstance.loadDisplayFile()disposes the shown display, shows "Loading ...", and loads the new display in a background job, but nothing kept track of that job. When a second load starts before the first one is done, for example with a double click on "back", both jobs represent their display and start its runtime:Closing the display while it loads also gave a "Cannot load model" error dialog after the display was gone.
The load sequence stays as it is: the shown display is disposed and "Loading ..." is shown right away, the file is loaded in the background, and neither the loads nor the UI thread wait for each other. What's new:
Job. A new load, or closing the display, cancels it (Job.cancel(), as in the logbook search).DisplayRuntime.stop()skips it whileStarting). If the display is disposed during that start, the UI thread only disposes the representation and the load job stops the runtime and disposes the model once the start is done. The UI thread doesn't wait for the start, which matters for PV types that connect while they are created.Testing
DisplayLoadSequenceUI(TestFX), 5 tests. Two loads in a row, a replaced load that fails, closing a display while it loads, and a newer load while the previous runtime is still starting (with a test PV type whose creation blocks) fail on master and pass with this PR. One test checks that the shown display's PVs are released and "Loading ..." is shown before the new widgets, on master and with this PR.Not changed here, the same as on master:
loadDisplayFile()and has a similar window between representing and starting.Checklist
The tests follow the
*UInaming of theui-testsprofile. That profile currently runs no tests (failsafe 2.22.0 can't discover JUnit 5 tests with the current JUnit platform, also for the existing UI tests incore/ui), so they were run with surefire under Xvfb.